0.6/1 kV Halogen Free XLPE Insulated Power Cables (N2XH)

N2XH (VDE)

0.6/1 kV halogen free XLPE insulated power cables (N2XH) are designed for power
transmission and distribution in fixed installations where enhanced fire safety,
low smoke emission, and high thermal performance are required. These cables combine
XLPE insulation with halogen free materials to provide improved current carrying
capacity and reduced toxic gas emission in case of fire.

N2XH cables are widely used in public buildings, industrial facilities, and
infrastructure projects where human safety and system reliability are critical.

Applications

  • Power transmission and distribution systems
  • Public buildings such as hospitals, schools, and airports
  • Industrial facilities and plants
  • Commercial and residential buildings
  • Infrastructure and utility projects
  • Areas requiring low smoke and halogen free cables

N2XH cables are preferred in installations requiring high fire safety standards,
low smoke density, and reliable electrical performance.

Cable Construction

  • Conductor: Solid or stranded copper conductor
  • Insulation: XLPE (Cross-Linked Polyethylene)
  • Inner Sheath: Halogen free compound
  • Outer Sheath: Halogen free compound

N2XH cables are constructed with XLPE insulated copper conductors and halogen free
inner and outer sheaths. This design provides excellent thermal performance,
mechanical protection, and minimal smoke and toxic gas emission during fire.

ParameterValue
Rated Voltage0.6/1 kV
Conductor MaterialCopper (Cu)
Conductor TypeSolid or Stranded
Insulation MaterialXLPE
Inner SheathHalogen Free Compound
Outer SheathHalogen Free Compound
Operating TemperatureMax. +90 °C
Short Circuit TemperatureMax. +250 °C
Installation TypeFixed installation
Smoke DensityLow smoke
Halogen ContentHalogen free
Flame RetardantIEC 60332-1
ParameterDescription
Conductor Resistance at 20°CAccording to IEC 60228
Insulation Resistance≥ 20 MΩ·km
Test Voltage3.5 kV
Current Carrying CapacityHigher than PVC insulated cables
StandardDescription
VDEN2XH
IEC 60502-1Low Voltage Power Cables
IEC 60332-1Flame Retardant
CECompliant
RoHSCompliant
Application Area
Public buildings
Industrial facilities
Infrastructure projects
Commercial buildings
Areas with high fire safety requirements
Nominal Cross Section (mm²)Overall Diameter mm (approx.)Net Weight kg/km (approx.)Conductor DC Resistance at 20°C (max. ohm/km)Current Carrying Capacity in Air (A)Current Carrying Capacity in Ground (A)
1 Core
1×46.7774.614456
1×67.2983.085671
1×108.511421.837796
1×169.02001.15102125
1×2510.53000.727136162
1×3511.63980.524168197
1×5013.15250.387203234
1×7015.07320.268258291
1×9517.210100.193315351
1×12019.112550.153365403
1×15021.015450.124420458
1×18523.519150.0991483521
1×24026.525150.0754573611
1×30029.531400.0601661697
1×40034.040200.0470780811
1×50038.051000.0366903930
1×63043.065500.028310451063
2 Cores
2×1.59.010512.12432
2×2.510.01387.413243
2×411.11854.614256
2×612.12453.085371
2×1014.53751.837496
2×1616.55351.1598125
2×2520.08300.727128162
2×3522.110850.524157197
2×5025.514500.387190234
3 Cores
3×1.59.512212.12432
3×2.510.51657.413243
3×411.72254.614256
3×612.83053.085371
3×1015.44721.837496
3×1617.56821.1598125
3×2521.210650.727128162
3×3523.514000.524157197
3×5027.218500.387190234
4 Cores
4×1.510.314812.12432
4×2.511.52057.413243
4×412.82854.614256
4×614.13903.085371
4×1016.86101.837496
4×1619.28851.1598125
4×2524.514200.727128162
4×3527.218700.524157197
4×5031.225300.387190234
4×7036.035800.268242291
4×9541.249300.193293351
4×12046.062500.153339403
4×15051.577400.124389458
4×18557.597500.0991444521
4×24066.0128500.0754522611
5 Cores
5×1.511.217812.12432
5×2.512.52487.413243
5×413.63494.614252
5×614.94603.085364
5×1018.27221.837386
5×1621.010521.1596111
5×2525.015850.727130143
5×3528.121210.524160173
5×5037.028380.387195205
5×7037.240080.268247252
5×9542.053740.193305303
5×12048.068970.153355346
3.5 Cores (Reduced Neutral)
3×16+1018.28151.15 / 1.8398125
3×25+1622.112500.727 / 1.15128162
3×35+1624.115850.524 / 1.15157197
3×50+2528.021850.387 / 0.727190234
3×70+3532.130400.268 / 0.524242291
3×95+5036.641250.193 / 0.387293351
3×120+7040.552250.153 / 0.268339403
3×150+7044.563600.124 / 0.268389458
3×185+9550.080250.0991 / 0.193444521
3×240+12057.5104500.0754 / 0.153522611

Technical values are indicative and may vary depending on conductor size,
installation conditions, and applicable standards. For detailed technical data